Humidity Excursion - Bay 4B
1Sequence
| Time | Record |
|---|---|
| 17 Apr / 06:20 | Bay 4B upper sensor exceeded the preservation work-band. |
| 17 Apr / 06:44 | Adjacent sensors remained within band; aisle isolated from routine retrieval. |
| 17 Apr / 09:10 | Supply damper linkage found partially disengaged. |
| 18 Apr / 14:30 | Linkage replaced; environmental readings stabilized. |
| 19 Apr / 11:00 | Sampled enclosures cleared by Archive Preservation. |
2Holding review
Eleven enclosures nearest the upper sensor were inspected for dimensional change, adhesion, corrosion, and odor. No change was recorded. The enclosures were returned to their prior positions after shelf locations were reconciled against the retrieval ledger.
3Disposition
The event is closed as an equipment-maintenance exception. The affected sensor remains in service. The damper linkage has been added to the six-month visual inspection route.
4Limitations
Inspection was by sampling and cannot establish the condition of every sheet, plate, or storage medium in Bay 4B. No sealed enclosure was opened. This record does not change the archive holding count.